HVD Series
- 100kV, 200kV and 400kV Models
- High Input Impedance
- 25ppm Temperature Coefficient
- Corona Free Operation
- 0.5% Accuracy (higher accuracies available)
*Note: All specifications are subject to change without notice. Please consult the English PDF version of this datasheet for the most up-to-date revision.
Resistive Voltage Dividers
Resistive Voltage Dividers
...for the measurement of high voltages using a standard digital voltmeter*
Spellman's HVD Series of high voltage dividers provide laboratory or production facilities with a convenient method of measuring up to 100kVdc, 200kVdc or 400kVdc with accuracy better than 0.5%. These dividers are designed for use with high impedance digital voltmeters. All HVD dividers are housed in a polycarbonate cylinder containing a matched set of precision metal film resistors which have a temperature coefficient of less than 25 ppm. A ladder-type construction technique is used in conjunction with polished high voltage bushings specifically designed to minimize corona. BNC connectors are used to provide the low voltage proportional output signal.
The HVD Series of high voltage dividers have no inferred bandwidth measurement capability what so ever. They are intended for DC steady state measurement only.
Custom Encapsulated OEM High Voltage Dividers
Spellman designs and manufactures a wide array of custom encapsulated high voltage dividers for OEM applications like ion beam implantation for semiconductor manufacturing. Unique HV divider sizes, shapes, mounting arrangements and terminations can be provided addressing specific custom requirements. Contact Spellman to discuss your needs with our knowledgeable sales staff.
Calibration
Spellman provides an NIST traceable calibration certificate with each HVD. A yearly recalibration cycle is recommended. Contact Spellman for calibration services.
Specifications
(Ref. 128055-001 REV. M)
HVD
HVD100 | HVD200 | HVD400 | |
---|---|---|---|
Input Voltage | 0-100kVdc | 0-200kVdc | 0-400kVdc |
Input Impedance | 1000Mohms | 2000Mohms | 4000Mohms |
Output Impedance | 1M; 100kohms | 20kohms | 40kohms |
Output Taps | 100V, 10V | 2V | 4V |
Accuracy | 0.5%: (0.1% opt)1 | 0.5%: (0.25% opt)2 | 0.5% |
Stability | 0.01%/8hrs | 0.025%/8hrs | 0.025%/8hrs |
Temp. Coefficient | 25ppm/˚C | 25ppm/˚C | 25ppm/˚C |
Height | 17.5" (44.5cm) | 33.5" (84.5cm) | 61" (154.94cm) |
Max. Diameter | 10" (25.4cm) | 12" (30.5cm) | 20" (50.8cm) |
Weight | 6.75 lbs (3.1kg) | 12 lbs (5.5kg) | 24.45 lbs (11.8kg) |
Output Connector | BNC type | BNC type | BNC type |
Note: All specifications are subject to change without notice. Please consult the PDF version of this datasheet for the most up-to-date revision.
Tables & Diagrams
Frequently Asked Questions
What Are the Bandwidth Capabilities of the Hvd Series of High Voltage Dividers?